Rack Mounted Air And Liquid CDU-B
Model: XLX-J-FY016
1. Rated thermal exchange rate: 16.7KW
2. Rated water flow rate: 1.43m ³/h
3. Rated airflow rate: 4000m ³/h
4. Flow regulation range: 10-100%
5. Available head: primary side pressure drop ≤ 80kPa, secondary side ≥ 10m
6. Rated power: 1.17KW
7. Number of fans: 4
8. Available cooling media: deionized water/ethylene glycol solution/propylene glycol solution
9. Wind facing area of heat exchanger: 0.28 ㎡
10. Fin area of heat exchanger: 24.2 ㎡
11. Power specification: 220V AC/1PH/50Hz
Appearance specification: 10U